Skip Navigation Links

Case Study – Infiltration in a Raw Materials Warehouse


The challenge

A warehouse contains raw materials used in the manufacture of pharmaceutical products. The temperature in the warehouse must remain between 17°C and 25°C and the relative humidity must remain between 35% and 65%. A measurement survey showed that in winter the lower temperature and humidity limits were being breached at the bottom of the storage racks close to the east corner of the warehouse. Draughts of cold air could be felt at floor level in this corner. The air-conditioning system was becoming dilapidated. The warehouse owner needed to know whether the air-conditioning system was (a) no longer working properly and in need of replacement or (b) perfectly serviceable and being overwhelmed by a leaky building. Atkinson Science was asked to devise a programme of testing and computations to determine the most cost-effective way of bringing the warehouse back into compliance with the T and RH specifications.


The solution

Atkinson Science devised a programme of work designed to show whether the existing air-conditioning system was simply being overwhelmed by infiltration. If a building is very leaky then replacing the air-conditioning system may produce no benefit and be a costly mistake. The programme consisted of:

  1. A leakage survey to identify potential leakage paths into the warehouse;
  2. An air-tightness test conducted by BSRIA to determine the characteristic leakage curve of the warehouse;
  3. Estimation of the location and extent of leakage flows from the results of (a) and (b);
  4. Creation of a CFD model of the warehouse incorporating the leakages and the existing air-conditioning system. Validation of the model using the results of the measurement survey;
  5. Using the validated model to see whether a proposed new system would make an improvement when faced with the leakages.

The warehouse is shown in plan view in Figure 1. The warehouse has a floor area of 54 m × 38 m and a height of 10 m. The storage racks occupy only a third of the floor area. The rest of the space is taken up with offices. The storage area is ventilated by high-level diffusers, which are shown in Figure 1. There is a single extract vent, which is also shown. Goods are moved in and out of the warehouse through the roller-shutter doors at the east corner of the warehouse. The leakage survey identified numerous potential leakage sites. However, there were two sites, in particular, that were draughty and were clearly allowing in large volumes of air. The first was the join between the northeast wall and the concrete floor and the second was the bottom of the roller-shutter doors. The air-tightness test returned an air permeability Q50/Sp of 6.74 m3 h−1 m−2. According to CIBSE TM23:2000, this value represents good practice for large industrial buildings, but not best practice, which would require Q50/Sp to be 3.5 m3 h−1 m−2 or less. From the characteristic leakage curve the effective leakage area (EFA) was found to be 1.07 m2.


Fig 1  Plan of the raw materials warehouse

Plan of the raw materials warehouse

Leakages into a building can be caused by wind pressures on the building or by the difference in the internal and external temperatures (the stack effect). The stack effect will be greatest in winter and summer when the temperature difference is greatest and the taller the building the greater the stack effect. In winter, cold air will enter the building through openings at low level and warm air will leave through openings at high level. The draughts in the east corner of the warehouse were at floor level and were detected on a calm day in January, so we concluded that the draughts were being caused by the stack effect. The measurement survey showed that in winter the lower temperature and humidity limits were being breached at the bottom of the storage racks close to the East corner of the warehouse. These breaches are consistent with our conclusion that cold air was entering the warehouse at floor level under the stack effect.

We built a CFD model of the warehouse with the ventilation provided by the existing system. Figure 2 shows the computational domain. We distributed half the leakage area along the bottom of the northeast wall and the bottom of the roller-shutter doors and half along the wall at roof level. Assuming there was no wind pressure on the building, we calculated that 2.1 kg s−1 of air was entering the warehouse at low level and leaving at high level. Over the two-week period of the measurement survey the lowest outside temperature measured was −6.6°C. The relative humidity measured at the same time was 98.6%. We used these values as external boundary conditions.


Fig 2  Computational domain

Computational domain

The ventilation system supplies 10.7 m3 s−1 of conditioned air. A CFD computation involves an iterative process. At the end of each iteration we adjusted the supply temperature so that the computation achieved the measured average temperature in the warehouse (20.5°C). Then we adjusted the supply relative humidity so that the computation achieved the measured average relative humidity (38.3%). At the end of the computation the supply conditions were 26.8°C and 29.0% RH.

In winter the moisture content of the outside air is very low compared with the moisture content in the warehouse. At the outside conditions, −6.6°C, 98.6% RH, the moisture content is 2.12 g kg−1 dry air and at the average inside conditions, 20.5°C, 38.3% RH, the moisture content is 5.73 g kg−1 dry air. Consequently, we can easily identify the location of the leakage air in the warehouse by the drop in moisture content.

For the measurement survey the warehouse contained 54 T/RH loggers arranged in columns of three at the top, middle and bottom of the storage racks. Figure 3 shows the location of each column and the readings of the bottom loggers when the outside conditions are −6.6°C, 98.6% RH. We have also added the moisture content, calculated from the measured T and RH values. The highest temperatures are recorded in the storage rack closest to the office block and the temperature falls gradually towards the north and east corners of the warehouse. The average moisture content over the bottom loggers is 5.61 g kg−1 dry air. At location 11 in Figure 3 the moisture content falls to its lowest value of 4.23 g kg−1 dry air. We can show that the warehouse air must contain 22% by volume of outside air for the moisture content to fall from the average value to this value. Location 11 is the closest to the northeast wall and the roller-shutter doors where the draughts were felt.


Fig 3  Measured T, RH and moisture content for the bottom loggers

Measured T, RH and MC

Figures 4 and 5 give the temperature and moisture content computed by the CFD model in the same plane as the bottom loggers. A large swathe of cold air can be seen moving from the east corner of the warehouse towards the storage racks. However, the lowest moisture content in any of the racks (5.35 g kg−1 dry air) occurs at the end of the second rack from the office block, 4 metres from location 11. The computation is consistent with the measurements, but more of the infiltration flows across the front of the racks and less down the aisles between the racks. The average computed moisture content over the bottom loggers is 5.71 g kg−1 dry air, which compares well with the average measured value of 5.61 g kg−1 dry air. From these comparisons, we can conclude that we have specified the location and amount of infiltration reasonably well and that the CFD model provides an accurate representation of the temperature and humidity when the existing ventilation system is opposed by the infiltration.


Fig 4  Computed temperature in the plane of the bottom loggers for the existing air-conditioning system

Computed T for existing system


Fig 5  Computed moisture content in the plane of the bottom loggers for the existing air-conditioning system

Computed MC for existing system

We used the validated CFD model to determine how a proposed new ventilation system would perform when faced with the same infiltration. The proposed new system consists of 62 high-level diffusers supplying 10.7 m3 s−1 of conditioned air. At the end of the CFD computation the supply conditions were 27.3°C and 28.2% RH. Figures 6 and 7 show the computed temperature and moisture content in the same plane as the bottom loggers. Comparing Figures 4 and 6 shows that the temperature around the storage racks is less uniform with the new system, and especially around the racks on the northeast side of the warehouse. Comparing Figures 5 and 7 shows that more of the cold air is able to pass between the racks than before. In fact, there is a build-up of temperature in the north corner of the warehouse as warm air between the racks is pushed back by the flow of cold air. The average measured temperature over the bottom loggers is 20.2°C. When the existing system is replaced with the new system the average computed temperature falls from 19.9°C to 19.2°C because warm air is displaced upwards by the cold air. Clearly, the new system is less effective at dispersing the infiltration than the existing system. In fact, it is difficult to imagine any high-level ventilation system being able to disperse the cold air moving along the floor and we concluded that the warehouse must be sealed before deciding whether to replace the existing air-conditioning system with a new one.


Fig 6  Computed temperature in the plane of the bottom loggers for the new air-conditioning system

Computed T for new system


Fig 7  Computed moisture content in the plane of the bottom loggers for the new air-conditioning system

Computed MC for new system

The benefits

The programme of work by Atkinson Science showed that the warehouse must be sealed along its east side before any decision is made about replacing the air-conditioning system. It is possible that the existing system will perform perfectly well once the warehouse is sealed and that it would be more cost-effective to undertake some simple remedial work on the system than to replace it with a completely new system.